Introduction

Understanding the dynamics of heat pump COP is essential for anyone involved in HVAC system design or evaluation.
The Coefficient of Performance (COP) is a key metric for evaluating the energy efficiency of heat pumps. It represents the ratio between the thermal energy output and the electrical energy input. A higher COP indicates greater efficiency.

According to the International Energy Agency (IEA), increasing the heat pump COP by just 0.5 can reduce operating carbon emissions by around 7% (IEA, 2022). This article explores how ambient temperature and water outlet temperature—two fundamental variables—affect heat pump COP, drawing from thermodynamic principles, field data, and practical engineering perspectives.


1. Impact of Ambient Temperature: Heat Source Efficiency

1.1 Thermodynamic Background

Based on the Carnot cycle, the theoretical maximum heat pump COP is defined as:

COP_max = T_hot / (T_hot - T_cold)

Where T is absolute temperature in Kelvin. The formula reveals that the smaller the temperature lift between the source and the sink, the higher the efficiency.

In practice, real systems operate well below this theoretical maximum. According to the ASHRAE Handbook (2020), modern heat pumps typically achieve 40–60% of the Carnot limit, due to thermodynamic losses and component inefficiencies.

Engineering insight: The Carnot principle serves as a valuable benchmark, but real-world system behavior is driven by compressor performance, refrigerant thermophysical properties, and system control strategy.


1.2 Field Data

The European Heat Pump Association (EHPA) provides seasonal performance testing results that highlight the impact of falling ambient temperatures:

  • When outdoor temperature drops from 7°C to -7°C:

  • Air-source heat pump COP drops from 4.2 to 3.1 (−26%)

  • Ground-source COP declines from 5.1 to 4.3 (−16%)

These trends are widely observed in climate zones with high heating demand. For example, in southern Finland, several residential units recorded COP values below 2.0 during prolonged cold spells.
(Source: EHPA Market Report, 2023)


1.3 Mechanism of COP Reduction

Lower outdoor temperatures lead to significant drops in heat pump COP, driven by:

  • Reduced evaporating pressure, raising the compressor pressure ratio and increasing energy consumption

  • Decreased refrigerant mass flow, impairing heat transfer at the evaporator

  • Frequent defrost cycles, consuming auxiliary power and disrupting steady-state operation
    (Source: Journal of Building Engineering, 2021)

Design tip: In climates with seasonal lows below −10°C, systems should include vapor injection (EVI), optimized expansion valves, or hybrid solutions to stabilize performance.

heat_pump_COP_vs_temperature

2. Impact of Water Outlet Temperature: Load-Side Demands

2.1 Temperature vs. COP Curve

Raising the water outlet temperature increases the temperature lift the system must overcome, leading to lower heat pump COP and efficiency. According to Fraunhofer ISE:

                Water Outlet Temp            Typical COP Range     Relative COP Loss (vs. 35°C)
                                 35°C                                  4.0–4.8                                            —
                                 45°C                                  3.2–3.8                                       15–25%
                                 55°C                                  2.5–3.0                                       30–40%


(Source: Fraunhofer ISE White Paper, 2023)


2.2 Engineering Challenges in High-Temperature Operation

As outlet temperature rises:

  • Compressor discharge temperature may exceed 150°C, stressing thermal limits

  • System pressure increases, especially with R290 refrigerant where high-side pressure at 55°C can reach 26 bar

  • Lubricant breakdown risk rises due to high temperature and chemical interaction

Practical note: In high-temperature DHW applications, it's recommended to incorporate thermal buffers or cascade systems to reduce direct compressor load and extend equipment life.

COP_vs_water_temp (2)

3. Coupled Effects: Performance Under Extreme Conditions

Extreme temperature combinations pose a severe challenge to maintaining stable heat pump COP.


3.1 Combined Variables and Real-World Risk

According to simulations from ETH Zurich:

Risk scenario: A retrofit project in Innsbruck (Austria) showed that a standard air-to-water unit failed to maintain COP above 2.0 during a -12°C cold front with high DHW demand, leading to reliance on electric backup heaters.


3.2 Optimization Strategies

To improve heat pump COP in real-world conditions, a multi-pronged engineering approach is required.

A. Compressor Innovations

  • Inverter-driven compressors enable precise modulation to match real-time load

  • EVI (Economizer Cycle) enhances low-temp performance

  • Two-stage compression mitigates performance drops in extreme cold
    (Source: Applied Thermal Engineering, 2021)

B. Refrigerant Cycle Design

Deployment tip: For markets like Central Europe, using R290 in split-type or indirect loop systems combines low-GWP compliance with robust performance and higher heat pump COP.

你的段落文字

4. Design Guidance and Industry Outlook

4.1 Practical Design Considerations

  • Follow EN 14825 for seasonal performance benchmarks

  • Design for low supply temperatures (35–45°C) wherever possible

  • Explore hybrid integration, such as solar thermal preheating or gas backup

Planning insight: Heat pump COP should be considered under both mild and extreme seasonal test points. Systems should be rated not only at A7/W35, but also under worst-case A−10/W55 to ensure year-round reliability.


4.2 Innovation and Future Research

Future efforts are expected to focus heavily on raising heat pump COP under variable environmental loads. Emerging directions include:

  • AI-based COP prediction models to improve real-time control

  • Advanced refrigerants and phase-change materials

  • Standard evolution, such as IEC 63139, which addresses wide-range temperature test conditions

air souce heat pump

Conclusion

✅ Key Takeaways:

  • Ambient Temperature (7°C → -7°C) → heat pump COP drops 20–30%

  • Water Outlet Temp (35°C → 55°C) → heat pump COP drops 30–45%

  • Combined Conditions → heat pump COP may decrease up to 60%, energy use can double

To handle complex operating conditions, next-generation heat pump systems must prioritize improving heat pump COP through smarter system design and adaptive control. These systems require more intelligent control, climate-adaptive refrigerants, and resilient component design. Future-ready systems must integrate thermodynamic understanding, field-based optimization, and digital intelligence to deliver reliable efficiency across all seasons and geographies.


Optimize Your System with Confidence

Curious how to optimize heat pump COP and performance across extreme temperatures and outlet demands?
SolarEast offers engineered solutions tailored to your climate zone and system requirements.

Explore our advanced heat pump systems


Table of Content list

Contact Information

Add: NO.73 Defu Rd. Xingtan Town, Shunde District, Foshan City, Guangdong Province,P.R. of China
E-mail: heatpump@solareast.com
Contact Us
Copyright © 2023 Solareast Heat Pump Ltd. All Rights Reserved. Sitemap | Privacy Policy